CONTROL CONDENSATION WITH A CONSENSOR AND A COMPANION CIRCUIT MODULE

        CONDENSATION SENSOR ~ DEW SENSOR            CONDENSATION CONTROL ~ DEW MONITOR
          CONDENSATION MONITOR / DETECTOR
AVAILABLE OUTPUTS: 5 Volt Logic,  Open Collector,  or Relay Contacts
UNIQUE Sensor Monitoring Feature Offered On Some CIRCUIT MODULES
RELAY OUTPUTS:
Relay Contacts: Isolated Form C (SP/DT)
Rated at 3 amps 120 VAC, via 3 pigtail leads
(6" long nom for Model CM),
or 3 position Barrier strip for all other Modules.

LOGIC LEVEL OUTPUTS:
Pull up resistor (3K) to + 5 VDC)  When there is No CONDENSATION (or SENSOR FAULT) condition, output  = nom. 5 VDC.   When there is a CONDENSATION (or SENSOR FAULT) condition, output = < 0.4 VDC 

OPEN COLLECTOR OUTPUTS:  Solid State equivalent of "Voltage Free Contacts".
Max. voltage across output transistor with No CONDENSATION (or SENSOR FAULT) condition = 30 VDC.  Max. current through transistor when there is a CONDENSATION (or SENSOR FAULT) condition = 100mA.

POWER IN:
For Model CI- ICM,  9 to 28 VDC via input wires / cable.  Dissipates 10 / 50 milliwatts.
For Relay Modules,  nom. 12 VDC or VAC via a "concentric" (2.5 mm x 5.5 mm) power jack. 
A mating plug is provided unless the Model PM-A Power Module is ordered.
Draws Nom. 20 mA de-energized; to approx. 200 mA energized (with 2 relays energized).

POWER SUPPLY:
An optional plug-in "Model PM-A" power module is available. It supplies 12 VDC to its mating concentric power plug from a 120 VAC (US style) wall receptacle ("wall wart").

SIZE:
For relay modules;  Nom. 5.0" (12.7cm) x 2.7" (6.7 cm) x 0.9" (2.3 cm)  - except  for       Model ICM - R1 (or -R2) which is 2.0" (5.8 cm) High.  Distance between all module mounting holes - 4.5" (11.5 cm).

TEST:
Each Module has a form of circuit TEST.  All Modules except the Model CM, incorporate a unique "SENSOR FAULT" test feature as a separate output and indication.  Note:  Relay Modules with this SENSOR FAULT feature "Latch" the this output when it occurs.  It must be "RESET" (Button) after problem is attended to.

Operating Enviroment:
All circuit boards are conformally coated to resist moisture.

Operating Temperature: 0*C to 65*C

Alternate Configurations:
We are very applications oriented and will consider other configurations to suit
special applications

We are very Applications oriented and always eager to discuss yours, or to answer any questions.  Just Click the "CONTACT" button (top of page) to send an E-mail                or Telephone  (207) 733 2525  USA
Model CI- ICM - L   5 Volt Logic  (or -O   Open Collector)
A Model CI CONSENSOR with Integrated ICM Circuit Module.
Provides either 5 Volt Logic (- L) or
Open Collector (- O)  Outputs for both CONDENSATION condition and for "SENSOR FAULT" condition.  Perfect for control  systems (HVAC, refrig., etc.).
Provides relay contacts when used with
Model ICM-R1 (or-R2)  See below left.
Note: Open Collectors generally equate to the solid state version of "voltage free contacts"
Model CI- ICM shown with Model PA-3 Pipe Adapter.
Accepts Input from Model CI- ICM-L (above) to provide 2 (or 1) sets of Form C (SPST) relay contacts;
-- CONDENSATION & SENSOR FAULT --
Model ICM-R2  (or R1)
Model CMB-1  (or -2)
Accepts Input (Plug) directly from Model CI CONSENSORs and provides 1 (or 2) sets of Form C (SPST) relay contacts;
-- CONDENSATION & SENSOR FAULT --
All CIRCUIT MODULES above include a Bi-Color LED to indicate;                POWER,  CONDENSATION,  SENSOR FAULT
Model CM
Accepts Input (Plug) from Model C CONSENSOR or  Model CI CONSENSOR (with Plug Adapter) to proved a single set of Form C (SPST) relay contacts.  Red LED indicates CONDENSATION and circuit TEST
GENERAL INFORMATION
CHECK THE CONSENSOR / CIRCUIT MODULE CONFIGURATION CHART
     AT BOTTOM OF THIS PAGE FOR MORE SPECIFIC INFORMATION.
~ RELAY OUTPUT MODULES ~